2016-03-05 03:50:03 | 1) THE PLAN THAT WAS SUBMITTED NOTES A DELIVERY | | PRESSURE OF 5 PSI. THERE IS NO GAS TABLE IN THE 2014 | | FUEL GAS CODE FOR A 5 PSI TABLE FOR PE PIPE. SUBMIT 2 | | COPIES OF THE APPLICABLE SIZING TABLE USED FOR THE | | DESIGN OF THIS SYSTEM. FBC 107.2.1 FGC SEC.402.3. I | | CANNOT CHECK THE SIZING OF THE SYSTEM WITHOUT THE | | SIZING TABLE. | | 2) THE MANUF. SPECIFICATIONS FOR THE TANKLESS WATER | | HEATER MODEL IDENTIFIED GIVES A RANGE OF 15,000 BTU'S | | UP TO 180,000 BTU'S. IINDICATE THE SPECIFIC BTU LOAD ON | | THE PLANS FOR THE TANKLESS WATER HEATER AND ALSO THE | | RANGE ( MANUF. SPECS SHOW A BTU LOAD UP TO 20,000.) 3RD | | REQUEST. | | 3) SUBMIT TWO COPIES OF THE REVISED GAS DRAWING. ONLY | | ONE COPY HAS BEEN SUBMITTED. FBC 107.2.1. | | | | NOTE: SINCE THE PLANS HAVE BEEN REJECTED THREE TIMES | | FOR THE SAME ITEMS, A RESUBMITTAL FEE OF 4 TIMES THE | | PLAN REVIEW FEE IS REQUIRED TO BE PAID PER FL. STATUTE | | 553.80. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|