2016-03-03 11:05:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101,
 INCLUDING CHAPTER 43, BUIULDING REHABILITATION, AND ALL
 OTHER APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 2. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 A. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 B. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
 C. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3. SHEET FS 1.1 - 1.2 - THE INDICATED LOCATION OF THE
 EXISTING SPRINKLER HEADS AND NEW WALL LOCATIONS DO NOT
 APPEAR TO MEET THE CODE COVERAGE REQUIREMENTS OF NFPA
 13.
  
 PROVIDE A NOTE INDICATING FIRE SPRINKLER WORK SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
 4. SHEET E 1.0 - 1.2 - THE INDICATED LOCATION OF THE
 EXISTING FIRE ALARM DEVICES AND NEW WALL LOCATIONS DO
 NOT APPEAR TO MEET THE CODE COVERAGE REQUIREMENTS OF
 NFPA 72.
  
 PROVIDE A NOTE INDICATING FIRE SPRINKLER WORK SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS.
  
 5. THE NATURE OF THE REMODEL AFFECTS THE PREVIOSULY
 APPROVED LIFE SAFETY PLAN INCLUDING OCCUPANCY LOADS,
 COMMON PATHS OF TRAVEL, EXIT PATHS AND EXIT DOORS.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING COMPLIANCE
 WITH NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
  
  
  