Plan Review Notes For Permit 16020859 |
Permit Number |
16020859 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-07 08:58:15 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1.PLEASE CLARIFY IF THE EXISTING LIGHTING COMPLIES WITH | | THE AUTOMATIC MEANS OF CONTROL PER FBC ENERGY | | CONSERVATION 2014 5TH EDITION. 405.2 | | 2.SHOW THE EXISTING PANEL BOARDS UNDER SCOPE OF REMODEL | | FOR REFERENCE PURPOSE. LOADS ARE NOT REQUIRED AS NO | | ADDITIONAL LOADS ARE SHOWN. FBC 107.3.5 MINIMUM | | CRITERIA FOR PLAN REVIEW. | | 3.LABEL ON FLOOR PLAN THE CIRCUIT NUMBER DESIGNATION | | FOR LIGHTING AND POWER BEING RELOCATED. FBC 107.3.5 | | MINIMUM CRITERIA FOR PLAN REVIEW. | | 4.LABEL RECEPTACLE OUTLETS IN LOCKERS TO BE GFCI | | PROTECTED PER NEC 2011 210.8B(7) | | 5.ADDRESS FIRE COMMENTS REGARDING ELECTRICAL SHEETS. | | 6.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|