2016-03-07 08:58:15INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE CLARIFY IF THE EXISTING LIGHTING COMPLIES WITH
 THE AUTOMATIC MEANS OF CONTROL PER FBC ENERGY
 CONSERVATION 2014 5TH EDITION. 405.2
 2.SHOW THE EXISTING PANEL BOARDS UNDER SCOPE OF REMODEL
 FOR REFERENCE PURPOSE. LOADS ARE NOT REQUIRED AS NO
 ADDITIONAL LOADS ARE SHOWN. FBC 107.3.5 MINIMUM
 CRITERIA FOR PLAN REVIEW.
 3.LABEL ON FLOOR PLAN THE CIRCUIT NUMBER DESIGNATION
 FOR LIGHTING AND POWER BEING RELOCATED. FBC 107.3.5
 MINIMUM CRITERIA FOR PLAN REVIEW.
 4.LABEL RECEPTACLE OUTLETS IN LOCKERS TO BE GFCI
 PROTECTED PER NEC 2011 210.8B(7)
 5.ADDRESS FIRE COMMENTS REGARDING ELECTRICAL SHEETS.
 6.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  