2016-03-09 11:26:58INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHEET A1- PLEASE UPDATE ALL REFERENCES TO REFLECT
 CURRENT BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH
 EDITION FAMILY, NEC 2011.
 2. PLEASE CLARIFY ELECTRICAL SCOPE AND LABEL PLANS
 ACCORDINGLY. LABEL NEW OR EXISTING FOR EXAMPLE
 ELECTRICAL SERVICE MAIN AND INTERIOR DEVICES. FBC
 107.3.5
 3. IF ELECTRICAL SERVICE IS NEW PROVIDE AIC CALCULATION
 AND AIC RATING OF SERVICE EQUIPMENT. FBC RES E3606.3
 AND E3606.4
 4. PROVIDE MANUF. CUT SHEETS FOR TANKLESS WATER HEATER
 SHOWN. FBC 107.3.5
 5. PANEL SCHEDULE TO COMPLY WITH FBC RES E3706.2- ID
 CIRCUITS TO SHOW SPECIFIC PURPOSE OF USE. GENERAL
 LIGHTING DESIGNATION WILL NOT SUFFICE.
 6. PROVIDE A NOTE TO COMPLY WITH THE FBC EC
 CODE-R404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS.
 7. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  