Date |
Text |
2016-03-15 17:19:28 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF THE PAID RECEIPT IF FEES ARE DUE. |
| COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| DEVELOPMENT CODE. |
| |
| 2- SHEET D-1: |
| A) DRAINAGE PLAN: PROVIDE COMPLIANCE WITH THE OVERFLOW |
| SCUPPERS AS REQUIRED BY SEC. R903.4.1 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) ROOF FRAMING PLAN: SPECIFY ALL CONNECTORS FOR |
| TRUSSES, ROOF RAFTERS, LEDGERS, BEAMS AND COLUMNS, ETC. |
| SEC. R801.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| C) PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF |
| SHEATHING ON THE NEW ADDITION AND AREA TO HAVE NEW ROOF |
| TRUSSES SHOWING COMPLIANCE WITH THE TYPE OF NAIL AND |
| SPACING REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| D) FOUNDATION / FLOOR FRAMING PLAN: SPECIFY ALL |
| CONNECTORS FOR 2X LEDGERS TO THE NEW CONCRETE BEAM AND |
| TO THE EXISTING WALL. SEC. R601.2 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| E) SPECIFY TYPE OF WOOD TO BE USED FOR FLOOR FRAMING TO |
| SHOW COMPLIANCE WITH THE DECAY PROTECTION OF SEC. |
| R317.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 3- SHEET A-1: |
| A) PROVIDE COMPLETE WALL SECTION THROUGH NEW LAUNDRY |
| ADDITION THAT MATCHES PROPOSED CONSTRUCTION ON FRAMING |
| PLANS ON SHEET D-1. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) SPECIFY CARBON MONOXIDE ALARMS WITHIN 10'-0" OF ALL |
| BEDROOMS AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| |
| 4- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 5- DESIGNER OF RECORD TO SPECIFY THE DESIGN PRESSURES |
| FOR ALL EXTERIOR DOORS AND WINDOWS. SEC. R301 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| NOTE: PRODUCT APPROVALS WILL BE REVIEWED WHEN |
| INFORMATION IS PROVIDED. |
| |
| 6- SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS |
| AND SPECIFY THE ACTUAL SIZE OF THE PROPOSED CASEMENT |
| WINDOW (SEE PRODUCT APPROVAL SUBMITTED) TO VERIFY |
| COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 704 OF |
| FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) CASEMENT WINDOWS SPECIFIED ON PLANS. |
| CLARIFY IF BEDROOMS CASEMENT WINDOWS WILL HAVE MULLION |
| AS SHOWN ON REAR AND SIDE ELEVATION ON SHEET A-2. NOTE: |
| CASEMENT WINDOWS WITH MULLIONS DON'T COMPLY WITH |
| EGRESS. |
| |
| B) ARCHED "INSWING" ENTRY DOOR AS SHOWN ON PLANS. |
| |
| C) NEW LAUNDRY EXTERIOR DOOR AS SHOWN ON PLANS. |
| |
| D) DOUBLE FRENCH DOORS AS SHOWN ON PLANS. |
| |
| E) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY SIZE |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. SEC. |
| R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| F) ROOF TILE AS SPECIFIED ON PLANS. |
| |
| G) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF |
| RECORD ON ITEM #4 ABOVE. SEE ROOF TILE PRODUCT APPROVAL |
| FOR LISTED ADHESIVES. |
| |
| H) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT |
| GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| SEE CITY SAMPLE. |
| |
| I) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR ARCHITECT TO LIST THE FLORIDA PRODUCT |
| APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| |
| 8- CLARIFY WHERE IS THE EXTERIOR SWING DOOR FLORIDA |
| PRODUCT APPROVAL FL16674-R4 SUBMITTED GOING TO BE |
| INSTALLED. SEC. 107.2.1 CITY AMENDMENTS. ALSO, IF THIS |
| DOOR IS GOING TO BE USED, THEN PROVIDE COMPLETE |
| DRAWINGS. PAGES SHOWING TWO DRAWINGS PER SHEET ARE TOO |
| SMALL. PROVIDE ONE DRAWING PER PAGE. SEC. 107.2.1.4 |
| CITY AMENDMENTS. |
| |
| 9- CLARIFY WHERE ARE THE SLIDING GLASS DOORS NOA |
| 15-1013.15 SUBMITTED GOING TO BE INSTALLED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 10-- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN |
| WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 11- REAR ELEVATION ON SHEET A-2 DOESN'T MATCH FLOOR |
| PLAN. MISSING ONE WINDOW. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 12- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| THE CONSTRUCTION OF THE NEW AWNING BY THE MASTER |
| BEDROOM. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE NEW STEPS SHOWN ON PLANS. SEC. |
| R311.7.5 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T |
| STAPLE OLD DRAWINGS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |