Date |
Text |
2016-02-25 15:42:56 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16020780 |
| ADD: 214 ROSSEMARY BLVD. 6 TEST AUGER CAST CONCRETE |
| PILE |
| CONT: MOSS & ASSOCIATES |
| TEL: 954-868-5509 JAMES TURNER |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: THURS. FEB. 25/2016 |
| ACTION: BUILDING PROVISO |
| |
| 1) DURING THE PROCESS OF BORING OF THE TEST PILE TO THE |
| GROUTING PROCESS AND PLACEMENT OF RE-INFORCEMENT, THE |
| GEOTECHNICAL ENGINEER SHOULD ALSO MONITOR AND REPORT |
| THE RESULTS OF THE TEST PILE INSTALATION AS WELL AS |
| LOAD TESTING. THE WEST PALM BEACH BUILDING DEPARTMENT |
| WILL REQUIRE A SET OF BORING LOGS, PROVIDE THE |
| THEORETICAL PILE VOLUME AS WELL AS THE ACTUAL PILE |
| VOLUME FOR EACH TEST PILE AND TEST RESULTS OF THE 14 |
| INCH AND 24 INCH AUGER CAST CONCRETE TEST PILE. |
| |
| TABLE 5 SUMMARY OF PILE ALLOWABLE AXIAL CAPACITIES |
| INDICATES THE 14 INCH PILE MINIMUM PILE TIP ELEVATION |
| NGVD -40 FT AND THE 24 INCH PILE A -65 FT NGVD. SECTION |
| 6.2.2 INDICATES THERE IS A THIN LAYER OF COQUINA ROCK |
| AT THE SITE AND THE 24 INCH PILE MAY NEED TO GO AS DEEP |
| AS 75 TO 80 FEET TO ENSURE THE 24 INCH DIAMETER PILES |
| BE SOCKET AT LEAST 45 FEET INTO THE COQUINA. |
| |
| 2014 FBC-B 1810.3.5.2.2 UNCASED. CAST-IN-PLACE DEEP |
| FOUNDATION ELEMENTS WITHOUT A PERMANENT CASING SHALL |
| HAVE A DIAMETER OF NOT LESS THAN 12 INCHES (305 MM). |
| THE ELEMENT LENGTH SHALL NOT EXCEED 30 TIMES THE |
| AVERAGE DIAMETER. |
| |
| EXCEPTION: THE LENGTH OF THE ELEMENT IS PERMITTED TO |
| EXCEED 30 TIMES THE DIAMETER, PROVIDED THE DESIGN AND |
| INSTALLATION OF THE DEEP FOUNDATIONS ARE UNDER THE |
| DIRECT SUPERVISION OF A REGISTERED DESIGN PROFESSIONAL |
| KNOWLEDGEABLE IN THE FIELD OF SOIL MECHANICS AND DEEP |
| FOUNDATIONS. THE REGISTERED DESIGN PROFESSIONAL SHALL |
| SUBMIT A REPORT TO THE BUILDING OFFICIAL STATING THAT |
| THE ELEMENTS WERE INSTALLED IN COMPLIANCE WITH THE |
| APPROVED CONSTRUCTION DOCUMENTS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |