2016-02-19 13:17:19 | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-6718 | | [email protected] | | | | PROVIDE THE IMPACT SOUND TEST (ASTM E492-04) AND THE | | AIRBOURNE SOUND TRANSMISSION TEST RESULTS (ASTM E90-02) | | FOR THE PROPOSED QEP 72005Q NATURAL CORK UNDERLAYMENT | | SHEETS. | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | FBC 1207.2 AIR-BORNE SOUND. | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | E 90. | | | | |
|