2016-02-22 13:26:30 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1.PLEASE UPDATE ALL FBC 2104 5TH EDITION REFERENCES TO |
| THE ELECTRICAL NOTES ON SHEET E2.1E AS SHOWN ON |
| ARCHITECTURAL SHEETS. FBC 107.5.3 |
| 2.SHOW WINDOW RECEPTACLES REQUIRED PER NEC 210.62- |
| 220.14G, NOT SHOWN ON FLOOR PLAN OR PANEL LOAD |
| SCHEDULES. |
| 3.PLEASE PROVIDE SIZE OF THE SERVICE CONDUCTORS, |
| GROUNDING ELECTRODE CONDUCTOR, CONDUIT SIZES AND |
| FEEDERS TO BE LEGIBLE FOR THE SERVICE SHOWN, FBC |
| 107.3.5- NEC 310.15B16 TABLE, 250.22 TABLE. |
| 4.PROVIDE A NOTE ON RISER DIAGRAM TO BOND THE GAS |
| PIPING, PER NEC 250.104B |
| 5.SHOW ON PANEL SCHEDULES THE AIC RATING FOR ALL 3 |
| PANEL BOARDS. FBC 107.3.5 |
| 6.PLEASE CLARIFY PANEL B MCB 150AMPS. SHOW THE LOAD |
| CALCULATIONS ON PANEL A AS IT ORIGINATES THERE. SHOW |
| WHAT CIRCUIT SPACES ARE DESIGNATED FOR THIS 3 POLE |
| BREAKER FEEDING PANEL B. NEC 240.4 FBC 107.3.5 |
| 7.PROVIDE A WP/GFCI RECEPTACLE FOR SERVICE AT THE A/C |
| LOCATION WITHIN 25 FT OF UNIT PER NEC 210.63 |
| 8.COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| THIS PROJECT. |
| |