Notes |
Date |
Text |
2016-02-27 03:43:56 | 1) SUBMIT A SANITARY AND WATER RISER FOR THE ADDITION | | OF THE DRINKING FOUNTAIN ON THE FIRST FLOOR AND ANY | | OTHER CHANGES TO THE PLUMBING SYSTEM.. 2014 FBC SEC. | | 107.3.5.1.3. | | 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER | | THE 2014 FBC-ACCESSIBILITY SEC.211.2 OR THE | | INSTALLATION OF A HI-LO UNIT. | | 3) THE COFFEE MACHINE WATEER SUPPLY SHALL BE PROTECTED | | WITH A BACKFLOW PREVENTER PER 2014 FPC SEC.608.16.10. | | 4) SHT. P0.1 - PLUMBING FIXTURE SPECIFICATIONS - WATER | | COOLER NOTES REFER TO SEC.410.2 FOR AN EXCEPTION TO THE | | DRINKING FOUNTAIN REQUIREMENTS. THIS SECTION OF THE | | ACCESSIBILITY CODE REFERS TO PLATFORM LIFTS. CLARIFY. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|