Plan Review Notes For Permit 16020613 |
Permit Number |
16020613 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-26 09:40:14 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16020613 | | 2/26/16 | | | | 1) SHEET M1.2: THE SUPPLY AIR PLENUM FOR RTU- 2 CANNOT | | BE LOCATED IN THE FIRE-RATED ENCLOSURE OF STAIR #1- SEE | | SECTIONS 1022.5 AND 1022.6 FBC-14 BUILDING. | | 2) M1.2: IT APPEARS THAT FIRE DAMPERS ARE MISSING FOR | | THE SUPPLY AND RETURN DUCTS DROPPING INTO THE FIRST | | FLOOR FROM RTU-3. | | 3) M1.2: IT APPEARS THAT CORRIDOR 205 IS BEING USED AS | | A MEANS OF RETURNING AIR BACK TO RTU-2 FROM THE | | ADJOINING OFFICES AND COPY ROOM- SEE SECTION 601.2 | | MECHANICAL AND CORRECT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|