Plan Review Notes
Plan Review Notes For Permit 16020613
Permit Number 16020613
Review Stop M
Sequence Number 1
Notes
Date Text
2016-02-26 09:40:141ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020613
 2/26/16
  
 1) SHEET M1.2: THE SUPPLY AIR PLENUM FOR RTU- 2 CANNOT
 BE LOCATED IN THE FIRE-RATED ENCLOSURE OF STAIR #1- SEE
 SECTIONS 1022.5 AND 1022.6 FBC-14 BUILDING.
 2) M1.2: IT APPEARS THAT FIRE DAMPERS ARE MISSING FOR
 THE SUPPLY AND RETURN DUCTS DROPPING INTO THE FIRST
 FLOOR FROM RTU-3.
 3) M1.2: IT APPEARS THAT CORRIDOR 205 IS BEING USED AS
 A MEANS OF RETURNING AIR BACK TO RTU-2 FROM THE
 ADJOINING OFFICES AND COPY ROOM- SEE SECTION 601.2
 MECHANICAL AND CORRECT.
  