2016-02-23 06:24:07 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1.PLEASE LABEL FLOOR PLAN ROOM #112 RECEPTACLES WITHIN | | 6FT OF SINK TO BE GFCI PROTECTED PER NEC 210.8B5 | | 2.CLARIFY IF SHOW WINDOW RECEPTACLES REQUIRED PER NEC | | 210.62- 220.14G, NOT SHOWN ON FLOOR PLAN OR PANEL LOAD | | SCHEDULES. | | 3.SHOW ON FLOOR PLAN EXISTING WP/GFCI RECEPTACLE FOR | | SERVICE AT THE A/C LOCATION WITHIN 25 FT OF UNIT PER | | NEC 210.63, CIRCUIT H-8 | | 4.CLARIFY REQUIRED BRANCH CIRCUIT FOR DEDICATED SIGN | | OUTLET PER NEC 600.5A | | 5.PLEASE CORRECT PANEL SCHEDULE H-15, 17 THAT SHOWS A | | 60 AMP OVERCURRENT FOR THE RTU#3 WITH A #12 CONDUCTOR. | | CORRECT TYPO TO REFLECT ACTUAL CONDUCTOR SIZE BASED ON | | NEC 310.15B16. | | 6.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|