2016-04-04 16:01:14PLUMBING COMMENTS:
  
 1. SHT. P1-0 ROOM # 156 NOTES 3/4 CONDENSATE LINE
 DISCHARGING INTO MOP SINK CONDENSATE SHALL NOT
 DISCHARGE TO SANITARY.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 2.SHT. P1-1 PROVIDE SIZING CALCULATIONS FOR OIL
 SEPARATOR.
 SHALL COMPLY WITH FBC PL SEC.1003.4.2.2
  
 3. SHT. P2-1 RISER NO. 2 MISSING FLOOR DRAIN FOR PUMP
 ROOM #503 AND FLOOR DRAIN FOR WATER HEATER DRAIN ROOM
 #168.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 4.SHT. P1-3 IN THE BACK WALL OF BAY 17IT SHOWS A
 4"SANITARY STACK THE RISER ON SHT.P2-1 SHOWS IT AS A 2"
 PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 5. SHT P2-5 THE RISER DIRECTLY ABOVE RISER NO. 8 LABEL
 SHOWS 6" RWL WITH A 8" DISCHARGE SHT. P1-0 SHOWS THE
 SAME RWL AS 8" ON LINES 13 AND T PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC. 107.2.1