Plan Review Notes For Permit 16020572 |
Permit Number |
16020572 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-05-23 10:30:52 | 2ND REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1. PROVIDE SIZE AND LENGTH OF PIPE DOWN STEAM OF | | REGULATOR ON GAS LOG. FBC-2014 FUEL GAS, SECS. 402.4.1, | | 402.4.2. | | | | | | 2.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR COOK TOP | | AND GAS LOG. PER THE FBC-2014 FUEL GAS CODE SEC. 304. | | | | 3. SHOW ALL REGULATORS . FBC GAS SEC. 410.2 MP | | REGULATORS. MP PRESSURE REGULATORS SHALL COMPLY WITH | | THE FOLLOWING: 5. A TEE FITTING WITH ONE OPENING CAPPED | | OR PLUGGED SHALL BE INSTALLED BETWEEN THE MP REGULATOR | | AND ITS UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL | | BE POSITIONED TO ALLOW CONNECTION OF A | | PRESSURE-MEASURING INSTRUMENT AND TO SERVE AS A | | SEDIMENT TRAP | 2016-05-20 14:47:46 | NEW REVISED DRAWINGS SUBMITTED. JG. |
|