2016-05-23 10:30:522ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. PROVIDE SIZE AND LENGTH OF PIPE DOWN STEAM OF
 REGULATOR ON GAS LOG. FBC-2014 FUEL GAS, SECS. 402.4.1,
 402.4.2.
  
  
 2.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR COOK TOP
 AND GAS LOG. PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SHOW ALL REGULATORS . FBC GAS SEC. 410.2 MP
 REGULATORS. MP PRESSURE REGULATORS SHALL COMPLY WITH
 THE FOLLOWING: 5. A TEE FITTING WITH ONE OPENING CAPPED
 OR PLUGGED SHALL BE INSTALLED BETWEEN THE MP REGULATOR
 AND ITS UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL
 BE POSITIONED TO ALLOW CONNECTION OF A
 PRESSURE-MEASURING INSTRUMENT AND TO SERVE AS A
 SEDIMENT TRAP
2016-05-20 14:47:46NEW REVISED DRAWINGS SUBMITTED. JG.