2016-03-11 19:13:28 | RESIDENTIAL (R3) ALTERATIONS, MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- SHEET M-001: | | TRANSFER DUCT SIZE IN MASTER BEDROOM DOESN'T COMPLY | | WITH THE BALANCED RETURN AIR SEC. M1602.4 OF | | FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE: NEED TO | | CONSIDER ALL THE SUPPLY AIR GOING INTO THE MASTER | | BEDROOM TO SIZE THE TRANSFER DUCT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINE | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|