Plan Review Notes
Plan Review Notes For Permit 16020569
Permit Number 16020569
Review Stop G
Sequence Number 1
Notes
Date Text
2016-02-18 06:53:201) IDENTIFY THE PIPE MATERIAL ON THE PLAN FOR THE GAS
 DRYER AND THE WATER HEATER.2014 FBC SEC. 107.2.1.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE NEW GAS
 APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH 2014 FGC SEC. 301.3.
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 4) SIZE THE NEW GAS LINES TO THE WATER HEATER AND THE
 GAS DRYER.
 5) SIZE THE EXISTING GAS LINE IN ITS ENTIRETY TO ENSURE
 THE EXISTING GAS LINE IS ADEQUATE TO CARRY THE ADDED
 BTU LOAD. 2014 FBC SEC. 107.2.1.
 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE
 WATER HEATER AND THE DRYER. SUBMIT COMBUSTION AIR
 CALCULATIONS FOR THE DRRYER AND THE WATER HEATER. 2014
 FGC SEC.304.1.
 7) INDICATE ON THE PLAN IF ANY OF THE GAS PIPE WILL BE
 INSTALLED BELOW GROUND .FGC 107.2.1.
 8) IS THERE A CRAWL SPACE BELOW THIS STRUCTURE? IF SO,
 INDICATE ON THE PLAN IF THE GAS PIPE WILL BE INSTALLED
 WITHIN THE CRAWL SPACE AND SHOW THE TYPE OF PIPING TO
 BE INSTALLED WITHIN THE CRAWL SPACE. NOTE - P.E. PIPE
 CAN ONLY BE INSTALLED OUTSIDE UNDERGROUND IN ACCORDANCE
 WITH 2014 FBC SEC.404.17.1. P.E. PIPE CANNOT BE
 INSTALLED ABOVE GROUND IN A CRAWL SPACE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  