2016-02-17 13:25:21 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE AND | | THE SQUARE FOOT AREA OF THE ROOF THAT IS BEING REPLACED | | ON THE PERMIT APPLICATION. FBC 107.2.1 | | | | 2) SUBMIT TWO COPIES OF A DRAWING OF THE STRUCTURE'S | | ROOF AND SPECIFY THE AREAS OF THE ROOF THAT ARE TO BE | | RE-ROOFED. FBC 107.2.1 | | | | 3) CLEARLY SPECIFY THE SYSTEM THAT WILL BE INSTALLED | | AND IT'S MAXIMUM DESIGN PRESSURE, BY MARKING IT ON THE | | PRODUCT APPROVALS. FBC R905.11.3 | | | | 4) THERE HAS BEEN REVISIONS TO THE EVALUATION REPORT | | THAT WAS SUBMITTED FOR FL 2533. EVALUATION REPORT | | 3520.03.04-R14 FOR FL2533-R-13 WAS SUBMITTED AND THE | | CURRENT ONE IS EVALUATION REPORT 3520.03.04-R16 FOR | | FL2533-R-15. DCA RULE 9N-3 | | | | 5) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION IS | | "REROOF WITH TRINTY". TRINITY/ERD IS THE NAME OF THE | | CONSULTING FIRM THAT TESTED AND EVALUATED THE | | CERTAINTEED ROOFING SYSTEM. THE DESCRIPTION SHOULD | | INDICATE THIS IS A REROOF OF THE FLAT ROOF AREAS WITH A | | MODIFIED BITUMEN SYSTEM. FBC 107.2.1 |
|