Plan Review Notes
Plan Review Notes For Permit 16020540
Permit Number 16020540
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-17 13:25:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE AND
 THE SQUARE FOOT AREA OF THE ROOF THAT IS BEING REPLACED
 ON THE PERMIT APPLICATION. FBC 107.2.1
  
 2) SUBMIT TWO COPIES OF A DRAWING OF THE STRUCTURE'S
 ROOF AND SPECIFY THE AREAS OF THE ROOF THAT ARE TO BE
 RE-ROOFED. FBC 107.2.1
  
 3) CLEARLY SPECIFY THE SYSTEM THAT WILL BE INSTALLED
 AND IT'S MAXIMUM DESIGN PRESSURE, BY MARKING IT ON THE
 PRODUCT APPROVALS. FBC R905.11.3
  
 4) THERE HAS BEEN REVISIONS TO THE EVALUATION REPORT
 THAT WAS SUBMITTED FOR FL 2533. EVALUATION REPORT
 3520.03.04-R14 FOR FL2533-R-13 WAS SUBMITTED AND THE
 CURRENT ONE IS EVALUATION REPORT 3520.03.04-R16 FOR
 FL2533-R-15. DCA RULE 9N-3
  
 5) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION IS
 "REROOF WITH TRINTY". TRINITY/ERD IS THE NAME OF THE
 CONSULTING FIRM THAT TESTED AND EVALUATED THE
 CERTAINTEED ROOFING SYSTEM. THE DESCRIPTION SHOULD
 INDICATE THIS IS A REROOF OF THE FLAT ROOF AREAS WITH A
 MODIFIED BITUMEN SYSTEM. FBC 107.2.1