Plan Review Notes
Plan Review Notes For Permit 16020523
Permit Number 16020523
Review Stop G
Sequence Number 2
Notes
Date Text
2016-03-16 06:00:221) ALL COMMENTS FROM THE PREVIOUS REVIEW MUST BE
 ADDRESSED.
 2) SUBMIT 2 COPIES OF THE SURVEY THAT SHOWS THE
 LOCATION OF THE GENERATOR AND THE DISTANCE FROM THE
 BUILDING WALL TO THE GENERATOR AND ALSO ANY WALL
 OPENINGS TO THE GENERATOR. 2014 FBC SEC. 107.1.
 3) THE MINIMUM DISTANCE OF THE GENERATOR TO THE
 BUILDING WALL SHALL BE 5 FT. PER NFPA 37 & 2014 FGC
 SEC. 616.1.
 GENERATORS : NFPA 37 - SEC.4.1.4
 ENGINES LOCATED OUTDOORS
 ENGINES AND THEIR WEATHERPROOF HOUSINGS IF PROVIDED,
 THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5
 FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE THE FOLLOWING
 CONDITIONS EXIST:
 (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE
 RESISTANCE RATING OF AT LEAST 1 HOUR.
 (2) THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 4) SUBMIT 2 COPIES OF THE GENERATOR INSTALLATION
 MANUAL. 2014 FBC SEC. 107.2.1.
 5) SUBMIT DOCUMENTATION FROM GENERAC FOR THIS GENERATOR
 MODEL THAT ALLOWS A REDUCTION OF THE REQUIRED DISTANCE
 FROM THE STRUCTURE AS MANDATED IN NFPA 37 SEC. 4.1.4.
 6) THE GENERATOR EXHAUST VENT SHALL BE LOCATED A
 MINIMUM OF 10 FEET FROM THE PROPERTY LINE; 3 FEET FROM
 EXTERIOR WALLS AND ROOFS AND 10 FEET FROM OPERABLE
 OPENINGS INTO BUILDINGS PER 2014 FLORIDA MECHANICAL
 CODE SEC.501.3.
 7) SHOW THE LOCATION OF THE GAS METER ON THE SURVEY.FBC
 SEC. 107.1.
 8) I AM QUESTIONING THE VALUE OF THIS JOB AT $950.00
 THIS SEEMS LOW FOR THIS TYPE OF INSTALLATION. SUBMIT A
 COPY OF THE SIGNED CONTRACT FOR THIS WORK. 2014 FBC
 SECTION 109.3. THE COST OF THE GENERATOR MUST BE
 INCLUDED IN THE VALUE EVEN IF IT IS BEING PROVIDED BY
 THE OWNER.
 9) REMOVE ALL THE OLD DOCUMENTS FROM THE PERMIT PACKAGE
 THAT ARE NO LONGER APPLICABLE AND SUBMIT 2 COMPLETE
 SETS OF PLANS FOR REVIEW. FBC 107.1.
  