2016-03-16 06:00:22 | 1) ALL COMMENTS FROM THE PREVIOUS REVIEW MUST BE |
| ADDRESSED. |
| 2) SUBMIT 2 COPIES OF THE SURVEY THAT SHOWS THE |
| LOCATION OF THE GENERATOR AND THE DISTANCE FROM THE |
| BUILDING WALL TO THE GENERATOR AND ALSO ANY WALL |
| OPENINGS TO THE GENERATOR. 2014 FBC SEC. 107.1. |
| 3) THE MINIMUM DISTANCE OF THE GENERATOR TO THE |
| BUILDING WALL SHALL BE 5 FT. PER NFPA 37 & 2014 FGC |
| SEC. 616.1. |
| GENERATORS : NFPA 37 - SEC.4.1.4 |
| ENGINES LOCATED OUTDOORS |
| ENGINES AND THEIR WEATHERPROOF HOUSINGS IF PROVIDED, |
| THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5 |
| FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM |
| STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| SEPARATION SHALL NOT BE REQUIRED WHERE THE FOLLOWING |
| CONDITIONS EXIST: |
| (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE |
| RESISTANCE RATING OF AT LEAST 1 HOUR. |
| (2) THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| NONCOMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED |
| THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| |
| 4) SUBMIT 2 COPIES OF THE GENERATOR INSTALLATION |
| MANUAL. 2014 FBC SEC. 107.2.1. |
| 5) SUBMIT DOCUMENTATION FROM GENERAC FOR THIS GENERATOR |
| MODEL THAT ALLOWS A REDUCTION OF THE REQUIRED DISTANCE |
| FROM THE STRUCTURE AS MANDATED IN NFPA 37 SEC. 4.1.4. |
| 6) THE GENERATOR EXHAUST VENT SHALL BE LOCATED A |
| MINIMUM OF 10 FEET FROM THE PROPERTY LINE; 3 FEET FROM |
| EXTERIOR WALLS AND ROOFS AND 10 FEET FROM OPERABLE |
| OPENINGS INTO BUILDINGS PER 2014 FLORIDA MECHANICAL |
| CODE SEC.501.3. |
| 7) SHOW THE LOCATION OF THE GAS METER ON THE SURVEY.FBC |
| SEC. 107.1. |
| 8) I AM QUESTIONING THE VALUE OF THIS JOB AT $950.00 |
| THIS SEEMS LOW FOR THIS TYPE OF INSTALLATION. SUBMIT A |
| COPY OF THE SIGNED CONTRACT FOR THIS WORK. 2014 FBC |
| SECTION 109.3. THE COST OF THE GENERATOR MUST BE |
| INCLUDED IN THE VALUE EVEN IF IT IS BEING PROVIDED BY |
| THE OWNER. |
| 9) REMOVE ALL THE OLD DOCUMENTS FROM THE PERMIT PACKAGE |
| THAT ARE NO LONGER APPLICABLE AND SUBMIT 2 COMPLETE |
| SETS OF PLANS FOR REVIEW. FBC 107.1. |
| |