Plan Review Notes For Permit 16020515 |
Permit Number |
16020515 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-18 09:49:14 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) IN THE 2014 FBC RESIDENTIAL CODE THE PRIVATE | | SWIMMING POOL ELECTRICAL PROVISIONS HAVE BEEN INSERTED | | IN CHAPTER 42. PLEASE UPDATE THE CODE REFERENCES. | | | | 2) NOTE 2 UNDER APPLICABLE CODES ON SHEET C-1, | | INCORRECTLY REFERENCES THE 2014 NEC. ELECTRICAL NOTE 1 | | ON SHEET N-1, ALSO INCORRECTLY REFERENCES THE 2014 NEC. | | THE CURRENT REFERENCED EDITION IS THE 2011 NEC. | | | | 3) THE SITE PLAN SHOWS AN OVERHEAD ELECTRICAL SERVICE | | DROP DIRECTLY OVER THE PROPOSED POOL. SHOW HOW | | COMPLIANCE WITH FBCR-E4203.6 FOR OVERHEAD CONDUCTOR | | CLEARANCES AND E4203.7 FOR UNDERGROUND WIRING. | | | | 4) SHOW COMPLIANCE WITH FBCR-E4203.1.2 FOR REQUIRED | | GFCI PROTECTED RECEPTACLE LOCATED A MINIMUM OF 6 FEET | | FROM AND NOT MORE THAN 20 FEET FROM THE INSIDE POOL | | WALL. | | | | 5) SHOW COMPLIANCE WITH FBCR-E4204.3 FOR THE BONDING OF | | THE POOL WATER. | | | | 6) THE EQUIPOTENTIAL BONDING NOTE ON SHEET P-3 | | REFERENCES THE 2008 NEC AND THE 2010 FBC. CITE THE | | CURRENT EDITIONS OF NEC AND FBC. | | |
|