2016-02-18 09:49:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN THE 2014 FBC RESIDENTIAL CODE THE PRIVATE
 SWIMMING POOL ELECTRICAL PROVISIONS HAVE BEEN INSERTED
 IN CHAPTER 42. PLEASE UPDATE THE CODE REFERENCES.
  
 2) NOTE 2 UNDER APPLICABLE CODES ON SHEET C-1,
 INCORRECTLY REFERENCES THE 2014 NEC. ELECTRICAL NOTE 1
 ON SHEET N-1, ALSO INCORRECTLY REFERENCES THE 2014 NEC.
 THE CURRENT REFERENCED EDITION IS THE 2011 NEC.
  
 3) THE SITE PLAN SHOWS AN OVERHEAD ELECTRICAL SERVICE
 DROP DIRECTLY OVER THE PROPOSED POOL. SHOW HOW
 COMPLIANCE WITH FBCR-E4203.6 FOR OVERHEAD CONDUCTOR
 CLEARANCES AND E4203.7 FOR UNDERGROUND WIRING.
  
 4) SHOW COMPLIANCE WITH FBCR-E4203.1.2 FOR REQUIRED
 GFCI PROTECTED RECEPTACLE LOCATED A MINIMUM OF 6 FEET
 FROM AND NOT MORE THAN 20 FEET FROM THE INSIDE POOL
 WALL.
  
 5) SHOW COMPLIANCE WITH FBCR-E4204.3 FOR THE BONDING OF
 THE POOL WATER.
  
 6) THE EQUIPOTENTIAL BONDING NOTE ON SHEET P-3
 REFERENCES THE 2008 NEC AND THE 2010 FBC. CITE THE
 CURRENT EDITIONS OF NEC AND FBC.
  