Plan Review Notes For Permit 16020455 |
Permit Number |
16020455 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-16 08:08:39 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16020455 | | 2/16/16 | | | | 1) PROVIDE THE SCOP RATING ON THE EQUIPMENT SCHEDULE | | FOR THE NEW LIEBERT SYSTEM- SEE TABLE C403.2.3(10) | | FBC-14 ENERGY CONSERVATION. | | 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | THE NEW CU-2 ON THE EXISTING EXTERIOR PAD.- SECTION | | 301.15 FBC-14 MECHANICAL. | | 3) PLEASE NOTE THAT THE PERMIT VALUE SHALL BE BASED ON | | LABOR, MATERIALS, AND EQUIPMENT, THEREFORE THE COST OF | | THE NEW 20-TON SYSTEM MUST BE INCLUDED IN THE TOTAL | | PROJECT COST- SECTION 109.3 WPB AMENDMENTS TO THE | | FBC-14 BUILDING CODE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|