2016-02-16 08:08:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020455
 2/16/16
  
 1) PROVIDE THE SCOP RATING ON THE EQUIPMENT SCHEDULE
 FOR THE NEW LIEBERT SYSTEM- SEE TABLE C403.2.3(10)
 FBC-14 ENERGY CONSERVATION.
 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE NEW CU-2 ON THE EXISTING EXTERIOR PAD.- SECTION
 301.15 FBC-14 MECHANICAL.
 3) PLEASE NOTE THAT THE PERMIT VALUE SHALL BE BASED ON
 LABOR, MATERIALS, AND EQUIPMENT, THEREFORE THE COST OF
 THE NEW 20-TON SYSTEM MUST BE INCLUDED IN THE TOTAL
 PROJECT COST- SECTION 109.3 WPB AMENDMENTS TO THE
 FBC-14 BUILDING CODE.
  