2016-03-04 13:08:3816020449
 7230 WINDING BAY LN.
 INTERIOR REMODEL
  
  
 PLANS ISSUED WITH THE FOLLOWING PROVISO.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 PROVIDE GFCI PROTECTED RECEPTACLES IN REMODELED BATH
 ROOMS. NEC 210.8; FBC R 3902
  
 VERIFY THE NEW HIGH HAT CEILING LIGHTING FIXTURES THAT
 ARE IN CONTACT WITH INSULATION ARE IC RATED. NEC
 410.116; FBC R 4004
  
 CEILING ELECTRICAL BOXES IF INTENDED FOR SUPPORT OF
 PADDLE FANS MUST BE LISTED FOR THAT USE. NEC 422.18;
 FBC R 3905.9
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  