Plan Review Notes For Permit 16020449 |
Permit Number |
16020449 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-04 13:08:38 | 16020449 | | 7230 WINDING BAY LN. | | INTERIOR REMODEL | | | | | | PLANS ISSUED WITH THE FOLLOWING PROVISO. | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 | | | | PROVIDE GFCI PROTECTED RECEPTACLES IN REMODELED BATH | | ROOMS. NEC 210.8; FBC R 3902 | | | | VERIFY THE NEW HIGH HAT CEILING LIGHTING FIXTURES THAT | | ARE IN CONTACT WITH INSULATION ARE IC RATED. NEC | | 410.116; FBC R 4004 | | | | CEILING ELECTRICAL BOXES IF INTENDED FOR SUPPORT OF | | PADDLE FANS MUST BE LISTED FOR THAT USE. NEC 422.18; | | FBC R 3905.9 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-373-3701 | | |
|