Notes
Date Text
2016-02-17 08:53:09THE BACKFLOW PREVENTION DEVICE SHALL BE LEAD FREE PER
 THE CITY OF WPB CROSS CONNECTION MANUAL. THE SUBMITTED
 SPECIFICATIONS DO NOT SHOW THE DEVICE AS LEAD FREE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  