Plan Review Notes
Plan Review Notes For Permit 16020422
Permit Number 16020422
Review Stop G
Sequence Number 1
Notes
Date Text
2016-02-13 06:14:421) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER . 2014 FBC SEC.
 107.2.1.
 2) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 AN INDOOR OR OUTDOOR MODEL.2014 FBC SEC. 107.2.1.
 3) IDENTIFY THE MODEL OF THE WATER HEATER ON BOTH SETS
 OF SPECIFICATIONS BY CIRCLING THE UNIT MODEL NUMBER
 .2014 FBC SEC. 107.2.1.
 4) INDICATE ON THE PLAN IF THE NEW UNIT IS REPLACING AN
 EXISTING GAS TANKLESS WATER HEATER OR IF IT IS
 REPLACING A GAS STORAGE TANK TYPE WATER HEATER. IF
 REPLACING A STORAGE TANK TYPE, A SEPARATE PERMIT WILL
 BE REQUIRED FOR THE REQUIRED ELECTRICAL WORK.
 5) SUBMIT A WATER AND GAS RISER DIAGRAM FOR CHANGES
 THAT MAY BE MADE TO THE GAS AND PLUMBING SYSTEMS. 2014
 FBC SEC.107.3.5.1.3.
 6) A COPY OF THE INSTALLATION MANUAL SHALL BE ONSITE
 FOR INSPECTION.2014 FGC SEC.305.1.
 7) IF THE NEW UNIT IS INDOORS, SUBMIT COMBUSTION AIR
 CLACULATIONS FOR REVIEW IN ACCORDANCE WITH 2014 FGC
 SEC.304.
 8) SUPPLY VENTING DETAILS FOR THE UNIT. SHOW TYPE OF
 VENT, SIZE, LOCATION, HEIGHT ABOVE ROOF, ETC. IN
 ACCORDANCE WITH THE MANUF.INSTALLATION MANUAL PER 2014
 FGC SEC.304.1 AND FGC SEC. 503.8.
 9) COMPLY WITH THE FOLLOWING ITEMS FOR GAS IF
 APPLICABLE.
 10) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 11)SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
 12) TYPE OF GAS (LP OR NATURAL).
 13) SHOW THE BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND
 THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. 15.
 14) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO THE CHIEF PLUMBING INSPECTOR AT
 561-805-6692.
  
 REV. 7/24/15 - TKL
  
  
  
  