2016-02-12 09:30:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE NOTE THAT THE ELECTRICAL CONTRACTOR QUALIFIER
 MUST SIGN DRAWINGS SUBMITTED NOT THE PROJECT MANAGER AS
 SHOWN. PER FBC 105.3.1.2 (FLORIDA STATUE 417.003 2H
 2. PROVIDE A NOTE TO INDICATE THE CARD READERS AND
 DATA/PHONES TO BE ON SEPARATE PERMIT. A NOTE WILL
 SUFFICE. FBC 107.
 3. PROVIDE A NOTE TO MAINTAIN FIRE RATING ON DEMISING
 WALLS. NEC 300.21
 4. IDENTIFY ROOM NAME AND NUMBER WHERE THE TEMPORARY
 OUTLETS WILL BE INSTALLED WITHIN HOSPITAL.
 5. CLARIFY ON PANEL SCHEDULE AND INDICATE BRANCH SYSTEM
 SERVING THE RECEPTACLES, EXAMPLE: CRITICAL/LIFE SAFETY,
 NORMAL. FBC 107
  