2016-02-24 16:28:10 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16020319 |
| ADD: 1800 PRESIDENTIAL WAY # 101 |
| CONT: LOWES HOME CENTER |
| TEL: 561-721-5611 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. FEB. 24/ 2016 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE WORK TO BE |
| PREFORMED UNDER THIS PERMIT IS TO INSTALL A WINDOW AND |
| SHUTTER. A SURVEY WAS SUBMITTED AND IT APPEARS THAT A |
| FENCE IS SHOWN AS THE WORK TO BE COMPLETED UNDER THIS |
| PERRMIT. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER.THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| PLEASE SUBMIT A FLOOR PLAN AS TO WHERE THE WORK IS |
| GOING TO TAKE PLACE. ALSO LABEL THE ROOMS AND SIZE OF |
| WINDOW TO BE REPLACED. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.: |
| 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| (1) FLOOR PLAN |
| (8) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE/ PRODUCT APPROVALS |
| |
| 2) WIND DESIGN REQUIREMENTS. 2014 FBC-B 1603.1.4 WIND |
| DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 2.2. RISK CATEGORY. |
| |
| 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 3) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR WINDOWS |
| AND SHUTTERS. 2014 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31) (B) WINDOWS |
| (E) SHUTTERS |
| |
| 4) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| GLAZING. FBC 1609.1.2. FL BLD CODE 2010 SECTION |
| 107.2.5.,1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 |
| PROCEDURES: A COMPLETE INSTALLATION SCHEDULE |
| SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |