2016-11-03 11:45:13 | RESIDENTIAL (R3) ALTERATION, THIRD MECHANICAL REVIEW |
| CHECKLIST. |
| CODE: FBC, 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY |
| MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC. |
| R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| RESPONSE: |
| CONTRACTOR'S RESPONSE LETTER STATES THAT MECHANICAL |
| CONTRACTOR WILL SUBMIT LOAD CALCULATIONS INFORMATION |
| UNDER A SEPARATE PERMIT. IF MECHANICAL CONTRACTOR IS |
| GOING TO APPLY FOR A SEPARATE PERMIT, THEN MECHANICAL |
| CONTRACTOR TO PROVIDE COMPLETE INFORMATION INCLUDING |
| EQUIPMENT SIZING CALCULATIONS AND A/C PLANS UNDER A |
| SEPARATE PERMIT. REMOVE A/C PLANS FROM THIS SUBMITTAL. |
| |
| |
| NOTE: |
| |
| COMMENTS BELOW FROM PREVIOUS CHECKLIST WERE NOT |
| REVIEWED ON REVISED PLANS SUBMITTED BECAUSE CONTRACTOR |
| STATED THAT MECHANICAL CONTRACTOR WILL APPLY FOR THE |
| SEPARATE PERMIT. PLEASE REMOVE THE A/C PLANS. |
| MECHANICAL CONTRACTOR TO SUBMIT PLANS ALONG WITH THE |
| EQUIPMENT SIZING CALCULATIONS AT TIME OF MECHANICAL |
| PERMIT APPLICATION. |
| |
| |
| 2- DRAWING M-1 SUBMITTED: |
| ORIGINAL COMMENT: |
| A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING |
| CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| RESPONSE: |
| REVISED PLAN SUBMITTED DOESN'T SHOW THE DUCT SIZES AND |
| LOCATION. NEED TO SHOW ALL DUCTWORK. |
| NOTE: BALANCE RETURN AIR REQUIREMENTS WILL BE REVIEWED |
| ONCE THE DUCTWORK IS PROVIDED. |
| |
| ORIGINAL COMMENT: |
| C) LABEL EACH FLOOR. FIRST AND SECOND FLOOR. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| RESPONSE; |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |