2016-11-02 16:15:46RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) NEED THE OWNER/AGENT CERTIFICATION AT THE BOTTOM OF
 THE FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NO ADDRESSED.
  
 B) ENERGY CALCULATIONS WERE PREPARED BY ANOTHER PERSON.
 PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) ITEM #15 IS TAKING THE CROSS VENTILATION CREDIT.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE CROSS VENTILATION AS REQUIRED BY
 SEC. R405.7.4 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 D) DOORS ON PAGE 3 OF 4 SHOW (2) 6'X 8 INSULATED DOORS.
 WHERE ARE THESE DOORS LOCATED ON PLANS. REVISED AS
 REQUIRED TO MATCH PLANS. ALSO, SEE PLANS AND DOOR
 PRODUCT APPROVALS SUBMITTED. R101. 5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. INFORMATION WAS NOT
 CHANGED. WHERE ARE THESE DOORS LOCATED ON PLANS? .
 ALSO, SEE PLANS FOR CORRECT ORIENTATION OF EXTERIOR
 DOORS. REVISE AS REQUIRED TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED.
  
 E) WINDOWS INFORMATION ON PAGE 3 OF 4 SHOWS VINYL
 WINDOWS. THIS DOESN'T MATCH PRODUCT APPROVALS
 SUBMITTED. REVISE AS REQUIRED. SEE PRODUCT APPROVALS
 SUBMITTED. SEC. R101. 5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 RESPONSE:
 NEW SINGLE HUNG FLORIDA PRODUCT APPROVAL FL14911.23 WAS
 SUBMITTED. NOTE: HISTORIC MAY NOT ALLOW VINYL WINDOWS.
 THIS WILL BE VERIFIED WITH HISTORIC. ON THE OTHER HAND,
 THERE WAS NOT PRODUCT APPROVAL SUBMITTED FOR THE NEW
 HORIZONTAL SLIDER WINDOWS SPECIFIED FOR THE SECOND
 FLOOR EGRESS WINDOWS. THEREFORE, UNABLE TO VERIFY IF
 THEY ARE GOING TO BE VINYL OR ALUMINUM.
  
 F) THE AIR BARRIER AND INSULATION INSPECTION COMPONENT
 CRITERIA CHECKLIST SUBMITTED WAS NOT COMPLETES. NEED TO
 BE COMPLETED. SEC. R405.4.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 G) PROVIDE COMPLETE EPL DISPLAY CARD AS REQUIRED BY
 SEC. R405.4.3 (1) FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 H) PROVIDE THE CORRECT CORRECT NAME OF THE BUILDER ON
 THE FRONT PAGE OF THE ENERGY CALCULATIONS. NOTE: ENERGY
 CALCULATIONS NAME "OWNER" AS THE BUILDER. "OWNER" IS
 NOT A BUILDER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED
 WHEN THE ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE
 DEFAULT FACTOR FOR GLAZING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. THERE ARE WINDOW
 MULLIONS ON DINING ROOM AREA AND STORAGE AREA. SEE
 PLANS.
  
 B) OUTSWING EXTERIOR DOORS AS SHOWN ON PLANS.
 RESPONSE:
 DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL13540-R3 DON'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD ON SHEET A-1/3. NEED PRODUCT
 APPROVAL FOR DOORS THAT MEET THE CALCULATED DESIGN
 PRESSURES.
  
 C) SINGLE HUNG WINDOWS.
 RESPONSE:
 NEW SINGLE HUNG FLORIDA PRODUCT APPROVAL FL14911.23 WAS
 SUBMITTED. THIS PRODUCT APPROVAL DOESN'T MEET THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD
 ON SHEET A-1/3. NEED PRODUCT APPROVAL FOR WINDOWS THAT
 MEET THE CALCULATED DESIGN PRESSURES.
 NOTE: HISTORIC MAY NOT ALLOW VINYL WINDOWS. THIS WILL
 BE VERIFIED WITH HISTORIC.
 NOTE: ORIGINALLY NOA 13-0430.09 WAS SUBMITTED FOR
 SINGLE HUNG WINDOWS. THIS NOA WAS ALREADY APPROVED.
 CLARIFY IF USING THE NOA THAT WAS ALREADY APPROVED OR
 IF NEW PRODUCT APPROVAL L WILL BE PROVIDED. DISCARD
 PRODUCT APPROVALS THAT WILL NOT BE USED.
  
 D) HORIZONTAL SLIDER WINDOWS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: PLEASE MAKE SURE SUBMITTED PRODUCT APPROVAL MEETS
 THE DESIGN PRESSURES AS SPECIFIED BY THE ENGINEER OF
 RECORD ON THE REVISED DRAWINGS. ALSO: CONFIRM WITH
 HISTORIC IF HORIZONTAL SLIDER WINDOWS ARE ALLOWED.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]