Plan Review Notes
Plan Review Notes For Permit 16020318
Permit Number 16020318
Review Stop M
Sequence Number 2
Notes
Date Text
2016-06-30 10:51:30RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
  
 NOTE:
 CONTRACTOR MAY SUBMIT COMPLETE HVAC INFORMATION UNDER A
 SEPARATE PERMIT. PLEASE ADVICE IF RE-SUBMITTING ALL THE
 REQUIRED INFORMATION NOW OR IF ALL THE INFORMATION WILL
 BE SUBMITTED BY THE MECHANICAL CONTRACTOR UNDER A
 SEPARATE PERMIT.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- DRAWING M-1 SUBMITTED:
 ORIGINAL COMMENT:
 A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 REVISED PLAN SUBMITTED DOESN'T SHOW THE DUCT SIZES AND
 LOCATION. NEED TO SHOW ALL DUCTWORK.
 NOTE: BALANCE RETURN AIR REQUIREMENTS WILL BE REVIEWED
 ONCE THE DUCTWORK IS PROVIDED.
  
 ORIGINAL COMMENT:
 C) LABEL EACH FLOOR. FIRST AND SECOND FLOOR. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE;
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  