Plan Review Notes For Permit 16020318
Permit Number 16020318
Review Stop E
Sequence Number 2
Notes
Date Text
2016-07-11 08:31:252ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS NOT ADDRESSED:
  
 2.CLARIFY IF ELECTRICAL SERVICE IS BEING UPGRADED.-
 PROVIDE ELECTRICAL PANEL LOAD CALCULATION. AIC RATING
 OF EQUIPMENT SERVICE. CONDUCTORS FEEDING INTERIOR PANEL
 SIZE. . CLARIFY NO GROUNDS TO AC, DRYER AND WATER
 HEATER?? LOADS
 3.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES-
 E3603.1
 4.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES-
 E3609.3
 6.2ND FLOOR, ADD WITHIN 3FT OF BASIN A RECEPTACLE
 BATHROOM OUTLET AT THE DOUBLE SINK LOCATION TO COMPLY
 WITH FBC RES E3901.6
 12.PROVIDE A PANEL SCHEDULE REFLECTING CIRCUIT
 IDENTIFICATION. FBC RES E3706.3
 13.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  