Plan Review Notes
Plan Review Notes For Permit 16020318
Permit Number 16020318
Review Stop M
Sequence Number 1
Notes
Date Text
2016-03-08 09:54:23RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 2- DRAWING M-1 SUBMITTED:
 A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) LABEL EACH FLOOR. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CONDENSING UNIT ANCHORING SPECIFICATIONS SHOWN ON
 THE A/C PLAN SUBMITTED: ENGINEER TO PROVIDE COMPLETE
 DETAIL AND SPECIFICATIONS SHOWING HOW THE CONDENSING
 UNIT IS ATTACHED TO THE CONCRETE SLAB THE WAY IS
 SPECIFIED. ARE THE TAPCONS ALONE HOLDING THE UNIT
 WITHOUT ANY REINFORCEMENT?. CLEARLY SPECIFY LOCATION
 AND NUMBER OF TAPCONS. PROVIDE ENGINEERING ANALYSIS
 SHOWING HOW THE UNIT WILL RESIST THE WIND LOADS THE WAY
 IT WAS SPECIFIED. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  