2016-03-08 09:54:23 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| COMMENTS. |
| CODE: FBC, 5TH EDITION (2014). |
| |
| 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY |
| MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC. |
| R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| 2- DRAWING M-1 SUBMITTED: |
| A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING |
| CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| |
| B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| C) LABEL EACH FLOOR. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- CONDENSING UNIT ANCHORING SPECIFICATIONS SHOWN ON |
| THE A/C PLAN SUBMITTED: ENGINEER TO PROVIDE COMPLETE |
| DETAIL AND SPECIFICATIONS SHOWING HOW THE CONDENSING |
| UNIT IS ATTACHED TO THE CONCRETE SLAB THE WAY IS |
| SPECIFIED. ARE THE TAPCONS ALONE HOLDING THE UNIT |
| WITHOUT ANY REINFORCEMENT?. CLEARLY SPECIFY LOCATION |
| AND NUMBER OF TAPCONS. PROVIDE ENGINEERING ANALYSIS |
| SHOWING HOW THE UNIT WILL RESIST THE WIND LOADS THE WAY |
| IT WAS SPECIFIED. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| |