2016-03-03 06:29:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE REFLECT NEC 2011 NOT NEC 2008 AS SHOWN.
 2.CLARIFY IF ELECTRICAL SERVICE IS BEING UPGRADED.
 3.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES-
 E3603.1
 4.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES-
 E3609.3
 5.PROVIDE GFCI PROTECTION FOR RECEPTACLES IN BATHROOM
 AREA. SEE 1ST FLOOR-FBC RES- E3902.1
 6.2ND FLOOR, ADD WITHIN 3FT OF BASIN A RECEPTACLE
 BATHROOM OUTLET AT THE DOUBLE SINK LOCATION TO COMPLY
 WITH FBC RES E3901.6
 7.2ND FLOOR; ADD A RECEPTACLE FOR WALL SPACE IN
 BEDROOM, WALL BEHIND THE DOUBLE VANITY. FBC RES
 E3901.2.2
 8.SHOW EGRESS LIGHTING OUTLETS PER FBC RES E3903.3
 9.PROVIDE A RECEPTACLE OUTLET WITHIN 25FT OF A/C
 EQUIPMENT PER FBC RES E3901.12
 10.CLARIFY SPACE ON 1ST FLOOR SHOWN WITH A FAN AND NO
 RECEPTACLE OUTLETS. LABEL AREA TO COMPLY WITH WALL
 SPACING REQUIREMENTS. FBC RES E3901.2.2
 11.PROVIDE ON DRAWINGS THE LOCATION OF SERVICE
 EQUIPMENT AND PANEL BOARD. FBC 107.3.5
 12.PROVIDE A PANEL SCHEDULE REFLECTING CIRCUIT
 IDENTIFICATION. FBC RES E3706.3
 13.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  