Plan Review Notes
Plan Review Notes For Permit 16020318
Permit Number 16020318
Review Stop B
Sequence Number 1
Notes
Date Text
2016-03-07 16:03:42RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PLEASE COORDINATE INFORMATION ON THE ENERGY
 CALCULATIONS AND PLANS TO AVOID CONFLICTS OR DELAYS.
  
 2- THE WIND SPEED SPECIFIED ON PLANS ON THE ENGINEERING
 NOTES BY THE TITLE BLOCK IS INCORRECT. CITY OF WEST
 PALM BEACH WIND SPEED IS 170 MPH NOT 160. REVISE AS
 REQUIRED. AND REVISE THE DOORS AND WINDOWS DESIGN
 PRESSURES ACCORDINGLY. SEC. R301.2.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SCOPE OF WORK IS NOT CLEAR. PLANS TO CLEARLY SPECIFY
 WHAT'S NEW AND WHAT'S EXISTING. CLEARLY IDENTIFY EACH
 ROOM SHOWN ON PLANS. CLEARLY SPECIFY ALL EXTERIOR DOORS
 AND WINDOWS TO BE REPLACED. ALSO, SPECIFY SIZE AND TYPE
 OF EXISTING WINDOWS (SPECIALLY BEDROOM WINDOWS) AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 4- A) EXISTING INTERIOR STAIR SECTION SHOWN ON SHEET
 A-2 DOESN'T MATCH STAIRS SHOWN ON FLOOR PLANS. ALSO,
 TREAD SIZE DIMENSION IS NOT CLEAR. SEE SEC. R311.7.5.2
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) FOR PROPER WAY
 OF DIMENSIONING THE TREAD AND REVISE AS REQUIRED.
  
 B) SPECIFY FIREBLOCKING IN STAIRS AS REQUIRED BY SEC.
 R302.11 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- STRUCTURAL NOTES ON SHEET A-2:
 A) THE LIVE LOADS SPECIFIED ARE INCORRECT. SEE TABLE
 R301.5 OF FBC-RESIDENTIAL, 5TH EDITION (2014) AND
 REVISE AS REQUIRED.
  
 B) UPDATE ALL THE SPECIFIED STANDARDS. SEE CHAPTER 45
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) FOR CURRENT YEAR
 OF STANDARDS ADOPTED AND REVISE AS REQUIRED.
  
 C) REVISE THE WIND SPEED. SEE ITEM #2 ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES AS SPECIFIED ON PLANS.
  
 B) METAL RIDGE VENTS AS SPECIFIED ON SHEET A-3.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 DETAILS SHOWN ON PLANS.
  
 E) "OUTSWING" EXTERIOR DOORS AS SHOWN ON PLANS. NOTE:
 NOA 09-0608.15 SUBMITTED IS FOR "INSWING" DOORS AND IS
 EXPIRED. NEED CORRECT AND CURRENT PRODUCT APPROVAL.
  
 F) FIXED WINDOWS. ACCORDING TO MIAMI-DADE WEBSITE THE
 FILE STATUS OF NOA 10-1015.02 SUBMITTED IS IN THE
 PROCESS OF BEING REMOVED. NEED TO PROVIDE CURRENT
 PRODUCT APPROVAL.
  
 G) "OUTSWING" EXTERIOR DOORS AS SHOWN ON PLANS.
 DRAWINGS FOR FLORIDA PRODUCT APPROVAL FL14569-R5
 SUBMITTED ARE FOR "INSWING" DOORS. NEED OUTSWING DOORS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]