2016-02-10 12:38:23FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 - NEC 230.2 NUMBER OF SERVICES. A BUILDING OR OTHER
 STRUCTURE
 SERVED SHALL BE SUPPLIED BY ONLY ONE SERVICE.PROPERLY
 IDENTIFY EACH SERVICE DISCONNECT. ( LABEL )
  
 - PLEASE TAKE A LOOK AT FPL APROVED RISER DIAGRAMS.
  
 - NEC 230.72 ALL DISCONNECTS MUST BE GROUPED.
  
 - NEC 250.94 PROVIDE INTERSYSTEM BONDING
  
 - NEC 215.5 PROVIDE A SITE PLAN SHOWING LOCATION OF
 EQUIPMENT RELATIVE TO EACH OTHER, PLEASE SHOW GROUNDING
 WIRE SIZE AND EXISTING LOAD CALCS.