Plan Review Notes For Permit 16020305 |
Permit Number |
16020305 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-10 12:38:23 | FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | - NEC 230.2 NUMBER OF SERVICES. A BUILDING OR OTHER | | STRUCTURE | | SERVED SHALL BE SUPPLIED BY ONLY ONE SERVICE.PROPERLY | | IDENTIFY EACH SERVICE DISCONNECT. ( LABEL ) | | | | - PLEASE TAKE A LOOK AT FPL APROVED RISER DIAGRAMS. | | | | - NEC 230.72 ALL DISCONNECTS MUST BE GROUPED. | | | | - NEC 250.94 PROVIDE INTERSYSTEM BONDING | | | | - NEC 215.5 PROVIDE A SITE PLAN SHOWING LOCATION OF | | EQUIPMENT RELATIVE TO EACH OTHER, PLEASE SHOW GROUNDING | | WIRE SIZE AND EXISTING LOAD CALCS. |
|