Plan Review Notes For Permit 16020274 |
Permit Number |
16020274 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-29 15:17:38 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | - ON DOUBLE SINKS IN BATHROOMS A GFCI MUST BE WITHIN 3 | | FT OF BASIN ( EITHER 1 ON EACH SIDE OR 1 IN THE MIDDLE. | | ) NEC 210.52 D | | | | - RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT AS WELL | | AS IC RATED AND SEALED TO NOT COMPROMISE BUILDING | | THERMAL ENVELOPE. ( 2 CFM ) FBC- ER 404.1.1 & 402.4.4 | | | | - PLEASE CLARIFY WHY ON THE FLOOR PLANS 2 50 AMP SUB | | PANELS ARE SHOWN AND RISER DIAGRAM REFLECTS 1. | | FURTHERMORE INCLUDE EXISTING SERVICE EQUIPMENT & PANEL | | BOARD LOCATIONS RELATIVE | | TO EACH OTHER ON ELECTRICAL FLOOR PLAN. WBA 107 | | | | - WHERE FANS ARE TO BE INSTALLED 70 POUND FAN RATED BOX | | SHALL BE MOUNTED AND PROPOERLY SECURED. |
|