Notes
Date Text
2016-02-09 12:18:241) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL THE
 FIXTURES TO BE REPLACED. 2014 FBC SEC. 107.2.1.FBC
 2) THE APPLICATION NOTES "INSTALL PLUMBING FOR LAUNDRY
 ROOM."THIS IS VAGUE. IS THIS AN EXISTING LAUNDRY ROOM
 OR IS A NEW LAUNDRY ROOM BEING CREATED? CLEARLY SHOW
 THE SCOPE OF WORK BEING DONE IN THE LAUNDRY ROOM ON THE
 PLAN.2014 FBC SEC. 107.2.1.
 3) THE APPLICATION NOTES "INSTALL TANKLESS WATER
 HEATER." IS THERE AN EXISTING TANKLESS WATER HEATER
 BEING REPLACED OR IS THIS TANKLESS REPLACEING A TANK
 TYPE WATER HEATER? IF IT IS REPLACING A TANK TYPE, THEN
 A SEPARATE ELECTRICAL PERMIT IS REQUIRED.
 4) IF ANY BATHTUBS ARE BEING REPLACED, WHAT TYPE OF
 REPAIR IS BEING DONE TO THE WALLS. INDICATE ON THE
 PLAN.2014 FBC SEC. 107.2.1.
 5) I AM QUESTIONING THE VALUE OF THIS JOB. SUBMIT A
 SIGNED CONTRACT SHOWING THE VALUATION OF THIS WORK.2014
 FBC SEC.109.3.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER.
  