Plan Review Notes For Permit 16020255 |
Permit Number |
16020255 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-09 10:51:07 | I SPOKE W/THE EC TO EXPLAIN THAT ALL NEC 404.2(C) | | REQUIRES THAT HE HAVE A NEUTRAL AT EVERY SWITCH OUTLET | | WHEN USING MC OR SIMILAR CABLE. FURTHERMORE I REMINDED | | HIM OF THE WPB 107.2.1 AMENDMENT. PLANS WILL BE SIGNED | | AT TIME OF PICK UP, |
|