Plan Review Notes For Permit 16020244 |
Permit Number |
16020244 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-12 16:54:25 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16020244 | | 2/12/16 | | | | 1) THE GRILLS IN THE ALLEN ROOM, & PM I & 2 ROOMS | | APPEAR TO BE UNDERSIZED PER SECTION 601.5 EXCEPTION #2 | | WHICH REQUIRES 50 SQ. IN. TO 100 CFM OF SUPPLY AIR. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|