Plan Review Notes
Plan Review Notes For Permit 16020244
Permit Number 16020244
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-18 13:41:14INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE PHONE
 AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 FBC 107.3.5
 2. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN
 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B5
 3. SHOW THE SIZE OF THE FEEDER CONDUCTORS TO BE AS PER
 NEC 310.15B16 ?3/0 FOR 200AMP SERVICE?
 4. CORRECT PANEL LOAD CENTER DESIGNATION TO REFLECT NEW
 NOT EXISTING, SHOW THE AIC RATING OF PANEL BOARD.FBC
 107.3.5
 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  