Plan Review Notes For Permit 16020244 |
Permit Number |
16020244 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-18 13:41:14 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | PERMITS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE PHONE | | AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. | | FBC 107.3.5 | | 2. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN | | 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B5 | | 3. SHOW THE SIZE OF THE FEEDER CONDUCTORS TO BE AS PER | | NEC 310.15B16 ?3/0 FOR 200AMP SERVICE? | | 4. CORRECT PANEL LOAD CENTER DESIGNATION TO REFLECT NEW | | NOT EXISTING, SHOW THE AIC RATING OF PANEL BOARD.FBC | | 107.3.5 | | 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|