2016-07-13 18:02:54 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBC | | 107.2.1 | | | | 2) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED | | RETURN AIR ON THE PLANS. SPECIFY THE SIZES OF THE | | TRANSFER DUCTS AND THEIR GRILLS ON THE MECHANICAL | | PLANS. FBC 107.2.1.3 | | |
|