2016-05-19 17:32:48PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY COMPLIANCE FORMS ARE REQUIRED TO BE
 SIGNED AND DATED BY THE OWNER OR AUTHORIZED AGENT
 LEGALLY DESIGNATED BY THE OWNER. FBC ENERGY
 CONSERVATION R103.1.1.2
  
 2) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBC
 107.2.1
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE SIZING CALCULATIONS. FBCR-M1401.3
  
 4) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED
 RETURN AIR ON THE PLANS.
  
  