Plan Review Notes For Permit 16020175 |
Permit Number |
16020175 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-05-19 17:32:48 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ENERGY COMPLIANCE FORMS ARE REQUIRED TO BE | | SIGNED AND DATED BY THE OWNER OR AUTHORIZED AGENT | | LEGALLY DESIGNATED BY THE OWNER. FBC ENERGY | | CONSERVATION R103.1.1.2 | | | | 2) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBC | | 107.2.1 | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT | | MATCHES THE SIZING CALCULATIONS. FBCR-M1401.3 | | | | 4) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED | | RETURN AIR ON THE PLANS. | | | | |
|