Plan Review Notes
Plan Review Notes For Permit 16020175
Permit Number 16020175
Review Stop B
Sequence Number 2
Notes
Date Text
2016-05-19 18:38:57PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED WITHIN 600 FEET OF THE
 INTER-COASTAL WATERWAY. SURFACE ROUGHNESS D PREVAILS IN
 THE UPWIND DIRECTION FOR AT LEAST 5,000 FEET.
 THEREFORE, THIS PROJECT IS CONSIDERED TO BE EXPOSURE
 CATEGORY D. FBC-R301.2.1.4.3 THE EXPOSURE CATEGORY HAS
 NOT BEEN CHANGED ON THE PLANS.
  
 2) REVIEW THE COMPONENT AND CLADDING WIND PRESSURES FOR
 EXPOSURE D AND REVISE AS REQUIRED. FBC-R301.2.1 THE
 COMPONENT AND CLADDING WIND PRESSURES HAVE NOT BEEN
 CHANGED ON THE PLANS.
  
 3) THE WINDOWS OF THE PROPOSED SECOND FLOOR BEDROOM
 ABOVE THE EXISTING LIVING ROOM ARE REQUIRED TO COMPLY
 WITH FBC-R310 FOR EMERGENCY ESCAPE AND RESCUE, THIS IS
 NOT INDICATED ON THE PLANS.
  
 4) PROVIDE DETAILS OF THE GUARDRAIL FOR THE MASTER
 BEDROOM BALCONY. FBC-R312
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. NO PRODUCT
 APPROVALS WERE SUBMITTED FOR THE STRUCTURAL MULLIONS.
  
 6) THE PLANS SPECIFY CEMENT ROOF TILES AND PRODUCT
 APPROVALS FOR TAMKO ASPHALT ASPHALT SHINGLES (NOA NO.
 11-1228.01) WERE SUBMITTED. THE PLANS WILL NEED TO BE
 REVISED AND THE ASPHALT SHINGLES WILL NEED TO BE
 APPROVED BY THE HISTORIC PLANNER.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2016-05-12 09:12:055/3/16 REVIEW COMMENTS DO NOT APPLY, PLEASE DISREGARD.
2016-05-03 13:14:25 
  
  
 1. NEED TO HAVE A CLEAN OUT AT THE BASE OF THE THREE
 INCH STACK FBC/ PLUMBING 708.3.4
  
 2 NEED DETAIL ON TUB DRAIN CONNECTION INSIDE SHOWER PAN
 AREA. CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 2010107.2.1
  
  
 3 NEED TO HAVE A VENT FOR THE W/M DISCHARGE FBC
 PLUMBING 901.2.1