Date |
Text |
2016-05-19 18:38:57 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PROJECT IS LOCATED WITHIN 600 FEET OF THE |
| INTER-COASTAL WATERWAY. SURFACE ROUGHNESS D PREVAILS IN |
| THE UPWIND DIRECTION FOR AT LEAST 5,000 FEET. |
| THEREFORE, THIS PROJECT IS CONSIDERED TO BE EXPOSURE |
| CATEGORY D. FBC-R301.2.1.4.3 THE EXPOSURE CATEGORY HAS |
| NOT BEEN CHANGED ON THE PLANS. |
| |
| 2) REVIEW THE COMPONENT AND CLADDING WIND PRESSURES FOR |
| EXPOSURE D AND REVISE AS REQUIRED. FBC-R301.2.1 THE |
| COMPONENT AND CLADDING WIND PRESSURES HAVE NOT BEEN |
| CHANGED ON THE PLANS. |
| |
| 3) THE WINDOWS OF THE PROPOSED SECOND FLOOR BEDROOM |
| ABOVE THE EXISTING LIVING ROOM ARE REQUIRED TO COMPLY |
| WITH FBC-R310 FOR EMERGENCY ESCAPE AND RESCUE, THIS IS |
| NOT INDICATED ON THE PLANS. |
| |
| 4) PROVIDE DETAILS OF THE GUARDRAIL FOR THE MASTER |
| BEDROOM BALCONY. FBC-R312 |
| |
| 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, |
| STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. NO PRODUCT |
| APPROVALS WERE SUBMITTED FOR THE STRUCTURAL MULLIONS. |
| |
| 6) THE PLANS SPECIFY CEMENT ROOF TILES AND PRODUCT |
| APPROVALS FOR TAMKO ASPHALT ASPHALT SHINGLES (NOA NO. |
| 11-1228.01) WERE SUBMITTED. THE PLANS WILL NEED TO BE |
| REVISED AND THE ASPHALT SHINGLES WILL NEED TO BE |
| APPROVED BY THE HISTORIC PLANNER. |
| |
| 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
2016-05-12 09:12:05 | 5/3/16 REVIEW COMMENTS DO NOT APPLY, PLEASE DISREGARD. |
2016-05-03 13:14:25 | |
| |
| |
| 1. NEED TO HAVE A CLEAN OUT AT THE BASE OF THE THREE |
| INCH STACK FBC/ PLUMBING 708.3.4 |
| |
| 2 NEED DETAIL ON TUB DRAIN CONNECTION INSIDE SHOWER PAN |
| AREA. CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| 2010107.2.1 |
| |
| |
| 3 NEED TO HAVE A VENT FOR THE W/M DISCHARGE FBC |
| PLUMBING 901.2.1 |