Plan Review Notes For Permit 16020175 |
Permit Number |
16020175 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-02 17:42:48 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AND | | EQUIPMENT SIZING CALCULATIONS FOR THE PROJECT. FBC | | ENERGY CONSERVATION R101.5.1.1 AND FBCR-M1401.3 | | | | 2) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBC | | 107.2.1 | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT | | MATCHES THE SIZING CALCULATIONS. FBCR-M1401.3 | | | | 4) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED | | RETURN AIR ON THE PLANS. | | | | 5) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL OF THE ENGINEER. COPIES | | AND OTHER FACSIMILES ARE NOT ACCEPTABLE. FS471 & FAC | | 61G15-23.002 | | | | 6) THE PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM 1/8 | | INCH SCALE PER FBC 107.2.1.4. | | | | |
|