Plan Review Notes
Plan Review Notes For Permit 16020175
Permit Number 16020175
Review Stop M
Sequence Number 1
Notes
Date Text
2016-03-02 17:42:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AND
 EQUIPMENT SIZING CALCULATIONS FOR THE PROJECT. FBC
 ENERGY CONSERVATION R101.5.1.1 AND FBCR-M1401.3
  
 2) SPECIFY THE DUCT AND GRILL SIZES ON THE PLANS. FBC
 107.2.1
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE SIZING CALCULATIONS. FBCR-M1401.3
  
 4) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED
 RETURN AIR ON THE PLANS.
  
 5) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL OF THE ENGINEER. COPIES
 AND OTHER FACSIMILES ARE NOT ACCEPTABLE. FS471 & FAC
 61G15-23.002
  
 6) THE PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM 1/8
 INCH SCALE PER FBC 107.2.1.4.
  
  