Plan Review Notes For Permit 16020145 |
Permit Number |
16020145 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-02-08 05:19:07 | 1) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. FBC SEC. | | 107.2.1. | | 2) HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED TO THE | | NEW SINK. FBC-PLBG. SEC. 607.1. | | 3) THE NEW SINK CANNOT BE INSTALLED ON A WET VENT PER | | 2014 FPC SEC.912.1, 912.1.1. THE NEW SINK SHALL BE | | STACKED AND VENTED AND CONNECT TO THE HORIZONTAL DRAIN | | DOWNSTREAM OF THE WATER CLOSET. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|