Plan Review Notes
Plan Review Notes For Permit 16020145
Permit Number 16020145
Review Stop M
Sequence Number 1
Notes
Date Text
2016-02-11 12:39:361ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020145
 2/11/16
  
 1) THE 10" TRANSFER DUCT FROM OFFICE #1 MUST BE
 ENLARGED TO 1.5 TIMES THE SIZE OF THE MAIN 10X10 SUPPLY
 DUCT INTO THE ROOM- SECTION 601.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  