2016-02-05 11:37:53 | 1ST ELECTRICAL REVIEW NOTES: |
| REVIEWED FOR COMPLIANCE WITH: |
| FBC 5TH EDITION 2014 |
| NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE |
| THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). |
| 2. YOU SHALL PROVIDE A SITE SPECIFIC RISER DIAGRAM AS |
| INDICATED IN NEC 215.5 THE RISER SHALL INCLUDE EVERY |
| ELECTRICAL PANEL AND SUBPANEL ALONG WITH FEEDER |
| CONDUCTOR SIZING & TYPE. LOAD CALCS SHALL BE PROVIDED |
| FOR EVERY PANEL. |
| 3. A CIRCUIT DIRECTORY AS REQUIRED IN NEC 408.4 SHALL |
| BE SUBMITTED. |
| 4. FBC-R315 REQUIRES THAT THERE BE A CARBON MONOXIDE |
| DETECTOR ?CO? WITHIN 10? OF THE BEDROOM DOORS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |