Notes |
Date |
Text |
2016-09-07 15:25:38 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16020141 | | 9/7/16 | | | | 1) THE RELOCATED GENERATOR ROOM EXHAUST DOES NOT APPEAR | | TO BE A MINIMUM 10' ABOVE THE WALKWAY AS REQUIRED BY | | SECTION 501.3.1 (2). PROVIDE A CLEARANCE DISTANCE | | MEASUREMENT FROM THE ADJOINING GRADE PLANE TO THE | | BOTTOM LIP OF THE DUCT OPENING. PLEASE NOTE THE EXHAUST | | IS ALSO PROHIBITED FROM BEING DIRECTED ONTO WALKWAYS | | PER SECTION 501.3.1.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|