2016-09-07 15:25:383RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16020141
 9/7/16
  
 1) THE RELOCATED GENERATOR ROOM EXHAUST DOES NOT APPEAR
 TO BE A MINIMUM 10' ABOVE THE WALKWAY AS REQUIRED BY
 SECTION 501.3.1 (2). PROVIDE A CLEARANCE DISTANCE
 MEASUREMENT FROM THE ADJOINING GRADE PLANE TO THE
 BOTTOM LIP OF THE DUCT OPENING. PLEASE NOTE THE EXHAUST
 IS ALSO PROHIBITED FROM BEING DIRECTED ONTO WALKWAYS
 PER SECTION 501.3.1.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  