Date |
Text |
2016-05-05 12:09:30 | 2ND REVIEW: FBC 2014 5TH ED |
| CHRISTOPHER S. THROOP, C.B.O. |
| BLDG. PLANS EXAMINER ? PX3169 |
| (561) 805-7918 |
| [email protected] |
| |
| 1. PROVIDE WIND LOAD ENGINEERING FOR NEW EXTERIOR |
| COMPONENTS. |
| |
| FBC 449.4.2.4.3 |
| ALL NEW ROOF APPENDAGES SUCH AS DUCTS, TANKS, |
| VENTILATORS, RECEIVERS, DX CONDENSING UNITS AND |
| DECORATIVE MANSARD ROOFS AND THEIR ATTACHMENT SYSTEMS |
| SHALL BE STRUCTURALLY ENGINEERED TO MEET THE WIND LOAD |
| REQUIREMENTS OF THE APPLICABLE BUILDING CODE. ALL OF |
| THESE ATTACHMENT SYSTEMS SHALL BE CONNECTED DIRECTLY TO |
| THE UNDERLYING ROOF STRUCTURE OR ROOF SUPPORT |
| STRUCTURE. |
| |
| FBC 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| |
| |