Plan Review Notes
Plan Review Notes For Permit 16020141
Permit Number 16020141
Review Stop M
Sequence Number 1
Notes
Date Text
2016-02-05 11:16:111ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #160201421
 2/5/16
  
 1) THE NEW W2 WALL AND ALL OTHER WALLS AND CEILINGS
 HOUSING THE EXTENDED GENERATOR ROOM MUST HAVE A MINIMUM
 1HR. FIRE-RESISTANCE RATING PER SECTION 4.1.2.1.1 NFPA-
 37. PLEASE REVISE THE PLANS ACCORDINGLY AND INCLUDE A
 MINIMUM 45 MINUTE FIRE-RATED DOOR WITH SELF CLOSING
 HARDWARE- SECTION 716 FBC-14 BUILDING. THIS NEW ROOM IS
 AN EXHAUST PLENUM FOR THE GENERATORS AND DOES NOT
 APPEAR TO BE SEPARATED BY FIRE-RATED CONSTRUCTION.
 2) PROVIDE UL TESTED AND APPROVED FIRE-STOPPING
 ASSEMBLIES FOR THE 56"X26" ROOM EXHAUST DUCT AND THE
 ENGINE EXHAUST PIPE THIMBLES PENETRATING FIRE-RATED
 WALLS. CLARIFY IF THE DUCT WILL HAVE A GRILL COVER AND
 PROVIDE A DETAIL.
 3) INDICATE THE DIAMETERS OF THE EXHAUST THIMBLES-
 MINIMUM 12" IS REQUIRED PER SECTION 8.3.3 (1) NFPA 37.
 4) PROVIDE DETAILS FOR BOTH THE ROOM EXHAUST AND ENGINE
 EXHAUST DUCTS: TYPE AND GAUGE OF STEEL, HANGER TYPES
 AND SIZES, SPAN OF HANGER SUPPORTS, REINFORCEMENT AND
 SEALING METHODS.
 5) PROVIDE AN ELEVATION VIEW OF THE EXHAUST OUTLETS
 INDICATING REQUIRED CLEARANCE DISTANCE MEASUREMENTS AS
 OUTLINED IN SECTION 501.3.1 FBC-214 MECHANICAL.
 6) PROVIDE APPROVED TERMINATION CAPS FOR THE ENGINE
 EXHAUST DUCTS- REFER TO SECTION 8.2.3 NFPA 37.
 7) PLEASE NOTE THE DRAWING INDEX INDICATES M1.2 WHCIH
 WAS NOT INCLUDED IN THE PLAN SETS. SHEET M3.1 WAS
 INCLUDED IN THE SETS BUT IS NOT SHOWN IN THE INDEX.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  