Plan Review Notes For Permit 16020117 |
Permit Number |
16020117 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-03-27 03:23:37 | 1) THE SPECIFICATION SHEETS FOR THE FEBCO LEAD PRESSURE | | FREE VACUUM BREAKER STATES THAT IT ONLY COMES IN SIZES | | 3/4" & 1" BUT THE PLANS CALL OUT AN 1 1/2" DEVICE. | | THEREFORE , THIS DEVICE CANNOT BE ACCEPTED OR APPROVED. | | FOR RESUBMITTAL, ENSURE THAT THE DEVICE YOU ARE | | PLANNING TO INSTALL IS AVAILABLE IN THE SIZE THAT YOU | | NEED. THE BFP DEVICE MUST BE THE SAME SIZE AS THE LINE | | TO WHICH IT IS CONNECTED. | | 2) THE PLANS CALL OUT FOR A ZURN/WILKINS MODEL 460 XL, | | BUT THE SPECIFICATIONS THAT YOU SUBMITTED ARE FOR A | | ZURN/WILKINS 420 XL. CLARIFY.SEE SHEETS LA-3 & LA-4 | | 3) THE ZURN/WILKINS 460 XL ALSO COMES IN THE LARGEST | | SIZE OF 1". JUST AN FYI. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | . |
|