2016-02-08 04:34:07 | 1) INDICATE ON BOTH SETS OF PLANS IF THE BACKFLOW |
| PREVENTER IS NEW OR EXISTING. IF THE BFP DEVICE IS NEW, |
| SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATION |
| SHEETS FOR REVIEW. |
| TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE |
| DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK |
| SECTION ON THE PERMIT APPLICATION. |
| 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. |
| 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF |
| SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES. |
| 4) CONTACT CITY OF WEST PALM BEACH UTILITIES FIELD |
| CUSTOMER SERVICE AT 561-822-2240 TO CONFIRM IF THE |
| DEVICE YOU ARE PURCHASING MEETS THE CITY'S |
| REQUIREMENTS. |
| 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED |
| IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND |
| CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH |
| PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO |
| ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE |
| DEVICE. |
| 6) PLACE THE CORRECT ADDRESS OF THE PROJECT ON THE |
| PLANS.FBC SEC. 107.2.1. |
| THE CITY OF WPB UTILITIES DEPARTMENT REVIEWS ALL NEW |
| BACKFLOW PREVENTER INSTALLATIONS. |
| NOTE: THE PERMIT CARD AND MANUFACTURER'S SPECIFICATIONS |
| SHALL BE ON THE JOBSITE FOR INSPECTION. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |