2016-02-05 08:54:451ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020105
 2/5/16
  
 1) REFER TO SECTION 513.4 FBC-14 MECHANICAL AND SUBMIT
 A RATIONAL ANALYSIS FROM A FL. LICENSED P.E. THAT
 DETAILS THE SMOKE CONTROL AND PRESSURIZATION SYSTEM
 DESIGN, HOW THE FANS WERE SIZED, METHODS OF OPERATION,
 SYSTEM SUPPORT ETC.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FANS
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR. REFER
 TO SECTION 513.10.5. AND SHOW COMPLIANCE:
 FANS: IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN
 FANS SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED
 FOR THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS
 BEING TWO. FANS SHALL BE SELECTED FOR STABLE
 PERFORMANCE BASED ON NORMAL TEMPERATURE AND, WHERE
 APPLICABLE, ELEVATED TEMPERATURE. CALCULATIONS AND
 MANUFACTURER'S FAN CURVES SHALL BE PART OF THE
 DOCUMENTATION PROCEDURES. FANS SHALL BE SUPPORTED AND
 RESTRAINED BY NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH
 THE STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT
 BE OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER
 (KILOWATTS) AS DETERMINED FROM MEASUREMENT OF ACTUAL
 CURRENT DRAW. MOTORS DRIVING FANS SHALL HAVE A MINIMUM
 SERVICE FACTOR OF 1.15.
 3) GUARDS MAY BE REQUIRED DEPENDING ON THE WHERE THE
 FANS ARE TO BE INSTALTED ON THE ROOF- A MINIMUM 10'
 CLEARANCE TO THE ROOF EDGES IS REQUIRED.
 4) PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE PLAN
 FOR TIE DOWN OF THE ROOF TOP FANS:WIND DESIGN CRITERIA
 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 A) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10B
 B) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719